Removing the redundant AC-power switch: 2145-CG8 or 2145-CF8

Use this topic when you need to remove a redundant AC-power switch on a SAN Volume Controller 2145-CG8 or 2145-CF8 node.

Before you begin

DANGER
Multiple power cords. The product might be equipped with multiple power cords. To remove all hazardous voltages, disconnect all power cords. (L003)
Multiple plugs: first set
or
Multiple plugs: second set
or
Multiple plugs: third set

Use the reference numbers in parentheses at the end of each notice (for example, D005) to find the matching translated notice in .

About this task

Note: The following procedure is applicable only for 2145-CG8 or 2145-CF8 nodes.
To remove a redundant AC-power switch, complete the following steps.

Procedure

  1. Turn off each IBM Spectrum Virtualize™ node that is connected by an uninterruptible power supply to the redundant AC-power switch. See MAP 5350: Powering off a node.
    1. One or two nodes might be connected to the redundant AC-power switch. If two nodes are connected to the redundant AC-power switch, you must ensure that both nodes are not in the same I/O group before you turn off the nodes. If the nodes are both turned off and they are in the same I/O group, the customer will lose access to the data that is managed by that I/O group.
    2. If both nodes that are powered by the redundant AC-power switch are in the same I/O group, turn off one node, disconnect it from the redundant AC-power switch, and connect it to a different power source. Then, turn the node back on. When it has recovered and rejoined the I/O group, it can maintain the I/O access when the other node is turned off and when the redundant AC-power switch is removed. When you perform this operation, pay particular attention to checking when it is safe to turn off the second node. See MAP 5350: Powering off a node.
  2. Remove both the redundant AC-power switch input-power cables from the site power distribution unit and unthread them in the rack, so they will slide out when the redundant AC-power switch is removed. There might be enough access to disconnect them from the redundant AC-power switch while it is in the rack, but often it is more convenient to leave them attached and remove them with the redundant AC-power switch.
  3. Remove the one or two redundant AC-power switches to 2145 UPS-1U power cables from the redundant AC-power switch. There is no need to disconnect them from the 2145 UPS-1U.
  4. Remove the four screws that hold the redundant AC-power switch in the rack. Be careful to support the redundant AC-power switch during this procedure because the screws are the only support for the unit.
  5. The redundant AC-power switch can be slid out of the rack along with the input-power cables if they are still attached.