Use this topic when you need to remove a redundant AC-power
switch on a SAN Volume Controller 2145-CG8 or 2145-CF8 node.
Before you begin
DANGER
Multiple power cords. The product might be equipped with multiple
power cords. To remove all hazardous voltages, disconnect all power cords. (L003)
Use the reference numbers in parentheses at the end of each notice (for example,
D005) to find the matching translated notice in .
About this task
Note: The following procedure is applicable only for 2145-CG8 or 2145-CF8 nodes.
To remove a
redundant AC-power
switch, complete the following
steps.
Procedure
- Turn off each IBM Spectrum Virtualize™ node
that is connected by an uninterruptible power
supply to
the redundant AC-power
switch.
See MAP 5350: Powering off a node.
- One or two nodes might be connected to the redundant AC-power
switch.
If two nodes are connected to the redundant AC-power
switch,
you must ensure that both nodes are not in the same I/O group before
you turn off the nodes. If the nodes are both turned off and they
are in the same I/O group, the customer will lose access to the data
that is managed by that I/O group.
- If both nodes that are powered by the redundant AC-power
switch are in the same I/O group, turn
off one node, disconnect it from the redundant AC-power
switch, and connect it to a different
power source. Then, turn the node back on. When it has recovered and rejoined the I/O group, it can
maintain the I/O access when the other node is turned off and when the redundant AC-power
switch is removed. When you perform this
operation, pay particular attention to checking when it is safe to turn off the second node. See
MAP 5350: Powering off a node.
- Remove both the redundant AC-power
switch
input-power
cables from the site power distribution unit and unthread them in the rack, so they
will slide out when the redundant AC-power
switch is
removed. There might be enough access to disconnect them from the redundant AC-power
switch while it is in the rack, but
often it is more convenient to leave them attached and remove them with the redundant AC-power
switch.
- Remove the one or two redundant AC-power
switches to 2145
UPS-1U power
cables from the redundant AC-power
switch.
There is no need to disconnect them from the 2145
UPS-1U.
- Remove the four screws that hold the redundant AC-power
switch in
the rack. Be careful to support the redundant AC-power
switch during
this procedure because the screws are the only support for the unit.
- The redundant AC-power
switch can
be slid out of the rack along with the input-power
cables if
they are still attached.