Replacing a battery in a Storwize® V7000 Gen1 power
supply unit
This topic describes how to replace the battery in the
control enclosure power-supply unit.
Before you begin
DANGER
When working on or around the system, observe the following
precautions:
Electrical voltage and current from power, telephone, and communication cables
are hazardous. To avoid a shock hazard:
If IBM® supplied a power cord(s), connect power to
this unit only with the IBM provided power cord. Do not
use the IBM provided power cord for any other
product.
Do not open or service any power supply assembly.
Do not connect or disconnect any cables or perform installation, maintenance, or
reconfiguration of this product during an electrical storm.
The product might be equipped with multiple power cords. To remove all hazardous voltages,
disconnect all power cords.
Connect all power cords to a properly wired and grounded electrical outlet. Ensure that the
outlet supplies proper voltage and phase rotation according to the system rating plate.
Connect any equipment that will be attached to this product to properly wired outlets.
When possible, use one hand only to connect or disconnect signal cables.
Never turn on any equipment when there is evidence of fire, water, or structural
damage.
Disconnect the attached power cords, telecommunications systems, networks, and modems
before you open the device covers, unless instructed otherwise in the installation and
configuration procedures.
Connect and disconnect cables as described in the following procedures when installing,
moving, or opening covers on this product or attached devices.
To disconnect:
Turn off everything (unless instructed otherwise).
Remove the power cords from the outlets.
Remove the signal cables from the connectors.
Remove all cables from the devices.
To connect:
Turn off everything (unless instructed otherwise).
Attach all cables to the devices.
Attach the signal cables to the connectors.
Attach the power cords to the outlets.
Turn on the devices.
Sharp edges, corners and joints might be present in and around the system. Use care when
handling equipment to avoid cuts, scrapes and pinching. (D005)
CAUTION:
The battery is a lithium ion battery. To avoid possible explosion,
do not burn. (C007)
Attention: Although many components are hot-swappable, they are
intended to be used only when your system is not active (no I/O operations). If your system
is powered on and processing I/O operations, go to the management GUI and follow the fix
procedures. Initiating the replacement actions without the assistance of the fix procedures
can result in loss of data or loss of access to data.
Although many components are hot-swappable, they are intended to be used only
when the component is not active (no I/O operations). If your system is powered on and
processing I/O operations, go to the management GUI and follow the fix
procedures. Initiating the replacement actions without the assistance of the fix procedures
can result in loss of data or loss of access to data.
Be careful when you are replacing the hardware components that are
located in the back of the system. Do not inadvertently disturb or remove any cables that
you are not instructed to remove.
About this task
Each power supply unit in a control enclosure contains
an integrated battery that is used during temporary short-term power
outages. You must replace the battery with the exact same model.
To
replace the battery in the power supply unit of the control enclosure,
perform the following steps: