Installing the SAN Volume Controller 2145-DH8 in
a rack
After installing the support rails and the cable arm management assembly, you
can install the SAN Volume Controller 2145-DH8 node
in the rack.
Before you begin
CAUTION:
To avoid any hazard from the rack tipping forward when
devices are installed, observe all safety precautions for the rack into which you are installing
the device.
Procedure
To install the SAN Volume Controller 2145-DH8 node
in the rack, complete the following steps.
Place the SAN Volume Controller 2145-DH8 in
the rails on the rack.
Pull the slide rails forward until they click twice
into place.
Lift the node and carefully tilt it into position over
the slide rails. Line up the rear nail heads 2 on
the node with the rear slots 3 on the
slide rails.
Slide the node down until the rear nail heads slip into
the two rear slots.
Lower the front of the node 4 until
the other nail heads slip into the other slots on the slide rails.
Verify that the front latch 5 slides
over the nail heads.
Figure 1. Installing
the SAN Volume Controller 2145-DH8 node
in the slide rails of the rack
Lift the locking levers on the slide rails and push the
node 2 all the way into the rack until
it clicks into place.