Redundant AC-power environment requirements
Ensure that your physical site meets the installation requirements for the redundant AC-power switch.
The redundant AC-power switch requires two independent power sources that are provided through two rack-mounted power distribution units (PDUs). The PDUs must have IEC320-C13 outlets.
The redundant AC-power switch comes with two IEC 320-C19 to C14 power cables to connect to rack PDUs. There are no country-specific cables for the redundant AC-power switch.
The power cable between the redundant AC-power switch and the 2145 UPS-1U is rated at 10 A.
Redundant AC-power switch specifications
The following tables list the physical characteristics of the redundant AC-power switch.
Dimensions and weight
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
| 43 mm (1.69 in.) | 192 mm (7.56 in.) | 240 mm | 2.6 kg (5.72 lb) |
Ensure that space is also available in the rack for the side mounting plates on either side of the redundant AC-power switch.
| Location | Width | Reason |
|---|---|---|
| Left side | 124 mm (4.89 in.) | Side mounting plate |
| Right side | 124 mm (4.89 in.) | Side mounting plate |
Heat output (maximum)
The maximum heat output that is dissipated inside the redundant AC-power switch is approximately 20 watts (70 Btu per hour).