You can replace the 2145 UPS-1U only
after you remove the previous uninterruptible power supply.
Before you begin
Use the reference numbers in parentheses at the end of each notice (for example,
D005) to find the matching translated notice in IBM System Storage SAN Volume Controller Safety Notices.
DANGER
Uninterruptible power supply (UPS) units contain specific hazardous
materials. Observe the following precautions if your product contains a UPS:
The UPS contains lethal voltages. All repairs and service must be performed only by an
authorized service support representative. There are no user serviceable parts inside the
UPS.
The UPS contains its own energy source (batteries). The output receptacles might carry live
voltage even when the UPS is not connected to an AC supply.
Do not remove or unplug the input cord when the UPS is turned on. This removes the safety
ground from the UPS and the equipment connected to the UPS.
The UPS is heavy because of the electronics and batteries that are required. To avoid
injury, observe the following precautions:
Do not attempt to lift the UPS by yourself. Ask another service representative for
assistance.
Remove the battery, electronics assembly, or both from the UPS before removing the UPS
from the shipping carton or installing or removing the UPS in the rack. (D007)
CAUTION:
This part or unit is heavy but has a weight smaller than 18 kg
(39.7 lb). Use care when lifting, removing, or installing this part or unit. (C008)
About this task
Perform the following steps to replace the 2145 UPS-1U:
Procedure
Place the 2145 UPS-1U on
a flat, stable surface with the front of the 2145 UPS-1U facing
toward you.
On each side of the 2145 UPS-1U,
attach the long end of a mounting bracket to the 2145 UPS-1U using
four of the supplied M3 × 6 screws ( 2 in Figure 1).
Figure 1. Installing the UPS mounting brackets for the 2145 UPS-1U
Stand at the front of the rack and place the back of the 2145 UPS-1U onto
the support rails, and then slide the 2145 UPS-1U into
the rack.
At the front of the 2145 UPS-1U,
install the two mounting screws ( 1 in Figure 2).
Figure 2. Mounting screws for the 2145 UPS-1U
Remove the 2145 UPS-1U front
panel by pulling it towards you and to the left, as shown in Figure 3.
Note: If you are having difficulty pulling the right side of
the panel free from the 2145 UPS-1U,
insert a flat-blade screwdriver between the right side of the cover
and the frame and gently pry it free.
Figure 3. Removing the 2145 UPS-1U front
panel
Remove the protective tape from the internal battery connector
(circled in Figure 4).
Figure 4. The 2145 UPS-1U internal battery
connector with protective tape
Connect the internal battery connector (circled in Figure 5).
Figure 5. The 2145 UPS-1U with
internal battery connectors in place
Note: A small amount of arcing might occur when connecting the batteries. This is
normal and does not damage the unit or present any safety concerns.
Reinstall the front panel.
At the back of the 2145 UPS-1U,
connect the SAN Volume Controller power
cable to load segment 2 receptacle ( 3 in Figure 7).
If applicable, install the power cable-retention bracket (shown in Figure 6).
Note: The 2145 UPS-1U is
intended to maintain power on a single SAN Volume Controller node
until data can be saved to the local hard disk drive. Only SAN Volume Controller nodes
can be plugged in to the 2145 UPS-1U or
else the SAN Volume Controller cluster
malfunctions. You must attach only one SAN Volume Controller to
the 2145 UPS-1U,
and nothing else.
Figure 6. The 2145 UPS-1U cable
retention bracket connected to the 2145 UPS-1U
Reconnect the SAN Volume Controller signal
cable to the communication port ( 2 in Figure 7).
Reconnect the 2145 UPS-1U main
power cable, from either the power distribution unit or from the redundant AC-power switch,
into the input connector ( 1 in Figure 7).
Note: If the 2145 UPS-1U does not
seem to work, ensure that the power cable is connected properly or reconnect the power
cable.
Figure 7. 2145 UPS-1U (rear view)
The
2145 UPS-1U is now in standby mode with
the SAN Volume Controller offline. All indicators that
are shown in Figure 7 are off.
To turn on the 2145 UPS-1U,
press and hold the on/off button ( 7 in Figure 8).
On some versions of the 2145 UPS-1U,
you need a pointed device, such as a screwdriver, to press the on/off
button. The 2145 UPS-1U undergoes
a self-test, taking approximately five seconds, before the power-on
indicator 6 and the load indicators ( 1 and 2 )
light up permanently to indicate that the 2145 UPS-1U is
supplying power to the SAN Volume Controller.
The 2145 UPS-1U begins
to charge its battery while in normal mode.
Figure 8. 2145 UPS-1U front-panel assembly
Note: If the 2145 UPS-1U battery is not
sufficiently charged, the SAN Volume Controller node is
not able to join the cluster. The node displays Charging on its front
panel until the 2145 UPS-1U battery
reaches sufficient charge, which could take an hour. When the SAN Volume Controller node rejoins the cluster, it might
display Recovering on its front panel while the 2145 UPS-1U battery finalizes its
charge.