Checking the grounding of the node, uninterruptible power supply, and redundant AC-power switch
Ensure that you understand how to check the grounding of a SAN Volume Controller, the uninterruptible power supply, and the optional redundant AC-power switch feature.
About this task
DANGER
Multiple power cords. The product might be equipped with multiple
power cords. To remove all hazardous voltages, disconnect all power cords. (L003)

To test the
grounding of a SAN Volume Controller node, follow the
steps for the SAN Volume Controller configuration that
you are using. Before you start, confirm that you know the SAN Volume Controller model type, the uninterruptible
power-supply type, and whether you are using
redundant AC power. Determine the location of the signal cables that are attached to the SAN Volume Controller.
Note: SAN Volume Controller
2145-DH8 and SAN Volume Controller 2145-SV1 nodes do
not have an uninterruptible power
supply.
When you are asked to test the grounding continuity, use your local procedures to initiate the test. The test is successful if the measured resistance is 0.1 ohm or less.
Attention: Some electrical circuits can be damaged if the external signal cables are present at the SAN Volume Controller while it is undergoing a grounding
test.