Installing the redundant AC-power switch in the rack

You must install the redundant AC-power switch in the rear of the rack before you connect the redundant AC-power switch to the site power.

Before you begin

Complete the following steps to install the redundant AC-power switch in the rack:

Procedure

  1. Use the hardware location chart to determine where to install the redundant AC-power switch in the rack. The redundant AC-power switch can be installed horizontally in a rack slot or vertically in one of the side slots of the rack.
  2. Position the four “C” clips in the rack's mounting bar, as shown in Figure 1.
    Figure 1. Positioning the clips
    This figure shows how to position the clips
  3. Position the redundant AC-power switch in the rack first, pushing the cables through to the front of the rack. Mount in place, as shown in Figure 2, using the four M6 screws.
    Figure 2. Positioned in rack
    Positioned in rack