You must install the redundant AC-power
switch in
the rear of the rack before you connect the redundant AC-power
switch to
the site power.
Before you begin
Complete the following steps to install the
redundant AC-power
switch in the rack:
Procedure
- Use the hardware location chart
to determine where to install
the redundant AC-power
switch in
the rack. The redundant AC-power
switch can
be installed horizontally in a rack slot or vertically in one of the
side slots of the rack.
- Position the four “C”
clips in the rack's mounting bar,
as shown in Figure 1.
Figure 1. Positioning the
clips
- Position the redundant AC-power
switch in
the rack first, pushing the cables through to the front of the rack.
Mount in place, as shown in Figure 2, using the four
M6 screws.
Figure 2. Positioned in rack