Installing the 2145 UPS-1U in the rack

After you have completed the preparation procedures, you are ready to install the 2145 UPS-1U in the rack.

Before you begin

Attention: See Safety and environmental notices before you start the installation process. Use the reference numbers in parentheses at the end of each safety notice to find the matching translated notice. For the translation of the danger, caution, and attention notices, see the IBM Systems Safety Notices.
CAUTION:
The uninterruptible power supply contains its own energy source (sealed, lead-acid batteries). The output receptacles might carry live voltage, even when the uninterruptible power supply is not connected to an AC supply. (11)
CAUTION:
Do not remove or unplug the input cord when the uninterruptible power supply is turned on. Unplugging the input cord removes the safety ground from the uninterruptible power supply and the equipment connected to the uninterruptible power supply. (12)
CAUTION:
To reduce the risk of fire or electric shock, install the uninterruptible power supply in a temperature- and humidity-controlled indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). (13)
CAUTION:
To avoid any hazard from the rack tipping forward when devices are installed, observe all safety precautions for the rack into which you are installing the device.

About this task

Complete the following steps to install the 2145 UPS-1U in the rack.
Note: You might have already completed steps 3 through 6 if you used the Read Me First pamphlet, which is included with the 2145 UPS-1U.

Procedure

  1. Stand at the front of the rack and place the back of the 2145 UPS-1U onto the support rails, and then slide the 2145 UPS-1U into the rack.
    CAUTION:
    The 2145 UPS-1U weighs 16 kg (35.3 lb). If you feel unsure about lifting the uninterruptible power supply to its location in the rack, seek assistance or remove the battery to reduce its weight.
  2. At the front of the 2145 UPS-1U, install the two mounting screws (M6x10)  1  as shown in Figure 1.
    Figure 1. Mounting screws for the 2145 UPS-1U
    Mounting screws of the 2145 UPS-1U
  3. If you have not already connected the internal battery connector, remove the 2145 UPS-1U front panel, shown in Figure 2, by pulling the panel forward (1), then pushing to the left (2).
    Figure 2. Removing the 2145 UPS-1U front panel
    This figure shows how to remove the 2145 UPS-1U front panel
  4. Remove the protective label from the internal battery connector (shown in Figure 3).
    Figure 3. The 2145 UPS-1U internal battery connector with protective tape
    This figure shows the 2145 UPS-1U internal battery connectors with protective tape covering the connector
  5. Connect the internal battery connector (shown in Figure 4). Each end of the keyed connector has two wires: one red (+) and one black (−). Align the connector so that the two red wires are joined and the two black wires are joined .
    Note: A small amount of arcing might occur when connecting the batteries. This is normal and does not damage the unit or present any safety concerns.
    Figure 4. The 2145 UPS-1U internal-battery connector
    This figure shows the 2145 UPS-1U internal battery connectors
  6. Reinstall the front panel. You might first need to move the sliding section on the front of the 2145 UPS-1U to the closed position.
  7. At the back of the 2145 UPS-1U, plug the 2145 UPS-1U main-power connector into the power socket.

    The power socket is shown by  1  in Figure 5.

    The 2145 UPS-1U is in standby mode; so all indicators are off.

    Connect each 2145 UPS-1U for an I/O group to a different power source.
    Note: If the 2145 UPS-1U does not seem to work, ensure that the power cable is connected properly or reconnect the power cable.
    Figure 5. 2145 UPS-1U (rear view)
    This figure shows the rear view of the 2145 UPS-1U
    •  1  Main power connector
    •  2  Communication port
    •  3  Load segment 2 receptacles
    Attention: Ensure that you comply with the following requirements:
    • The voltage that is supplied to the 2145 UPS-1U must be 200 - 240 V single phase.
    • The frequency that is supplied must be 50 or 60 Hz.
    Notes:
    1. The 2145 UPS-1U has an integrated circuit breaker and does not require external protection.
    2. The 2145 UPS-1U is intended to maintain power on SAN Volume Controller nodes until data can be saved to the local hard-disk drive. Only SAN Volume Controller nodes can be plugged into the 2145 UPS-1U or the SAN Volume Controller clustered system will malfunction.
  8. Press and hold the on/off button ( 7  in Figure 6) for approximately five seconds. You might need a pointed device, such as a screwdriver, to press the on/off button. The front panel indicators cycle through a startup sequence while the 2145 UPS-1U conducts a self-test.
    Figure 6. 2145 UPS-1U front-panel assembly
    This figure shows the 2145 UPS-1U front-panel assembly.

    When the self-test is complete, the power-on indicator  6  and the load indicators ( 1  and  2 ) illuminate to indicate that power is being supplied by the 2145 UPS-1U. The 2145 UPS-1U is now in normal mode, and is charging its battery. If the battery indicator  4  is on and the alarm is sounding, the voltage range setting might not be correct. When a SAN Volume Controller is connected to the 2145 UPS-1U, the SAN Volume Controller automatically adjusts the voltage range setting. Take no action for this alarm condition unless it persists for more than 5 minutes after a SAN Volume Controller is connected to this 2145 UPS-1U and turned on.

  9. Repeat all of these steps to install additional 2145 UPS-1U units.