After you have completed the preparation procedures, you
are ready to install the 2145 UPS-1U in
the rack.
Before you begin
Attention: See
Safety and environmental notices before you
start the installation process. Use the reference numbers in parentheses at the end of each safety
notice to find the matching translated notice. For the translation of the danger, caution, and
attention notices, see the
IBM Systems Safety
Notices.
CAUTION:
The uninterruptible power
supply
contains its own energy source (sealed, lead-acid batteries). The output receptacles might carry
live voltage, even when the uninterruptible power
supply is not
connected to an AC supply. (11)
CAUTION:
Do not remove or unplug the input cord when the uninterruptible power
supply is turned on. Unplugging the input
cord removes the safety ground from the uninterruptible power
supply and the equipment connected to the uninterruptible power
supply. (12)
CAUTION:
To reduce the risk of fire or electric shock, install the uninterruptible power
supply in a temperature- and
humidity-controlled indoor environment, free of conductive contaminants. Ambient temperature must
not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). (13)
CAUTION:
To avoid any hazard from the rack tipping forward when devices
are installed, observe all safety precautions for the rack into which you are installing the
device.
About this task
Complete the following steps to install the
2145
UPS-1U in
the rack.
Note: You might have already completed
steps
3 through
6 if you used the
Read
Me First pamphlet, which is included with the
2145
UPS-1U.
Procedure
- Stand at the front of the rack and place the back of the 2145
UPS-1U onto
the support rails, and then slide the 2145
UPS-1U into
the rack.
CAUTION:
The 2145
UPS-1U weighs
16 kg (35.3 lb). If you feel unsure about lifting the uninterruptible power
supply to
its location in the rack, seek assistance or remove the battery to
reduce its weight.
- At the front of the 2145
UPS-1U,
install the two mounting screws (M6x10) 1 as
shown in Figure 1.
Figure 1. Mounting screws for the 2145
UPS-1U
- If you have not already connected
the internal battery connector, remove the 2145 UPS-1U front
panel, shown in Figure 2, by pulling the panel forward (1),
then pushing to the left (2).
- Remove the protective label from the internal battery connector
(shown in Figure 3).
Figure 3. The 2145
UPS-1U internal
battery connector with protective tape
- Connect the internal battery connector (shown in Figure 4). Each end of the keyed connector has two wires: one red (+) and one black (−). Align the connector so that the two red wires are joined and the two black wires are joined .
Note: A small amount of arcing might occur when connecting the batteries. This is normal and does not damage the unit or present any safety concerns.
Figure 4. The 2145
UPS-1U internal-battery
connector
- Reinstall the front panel. You might first need
to move the sliding section on the front of the 2145
UPS-1U to
the closed position.
- At the back of the 2145
UPS-1U,
plug the 2145
UPS-1U main-power
connector into the power socket.
The power socket is shown by 1 in Figure 5.
The 2145
UPS-1U is
in standby mode; so all indicators are off.
Connect
each
2145
UPS-1U for
an I/O group to a different power source.
Note: If the 2145
UPS-1U does
not seem to work, ensure that the power cable is connected properly
or reconnect the power cable.
Figure 5. 2145
UPS-1U (rear
view)
- 1 Main power connector
- 2 Communication port
- 3 Load segment 2 receptacles
Attention: Ensure that you comply with the following
requirements:
- The voltage that is supplied to the 2145
UPS-1U must be 200 - 240 V single phase.
- The frequency that is supplied must be 50 or 60 Hz.
Notes: - The 2145
UPS-1U has
an integrated circuit breaker and does not require external protection.
- The 2145
UPS-1U is intended to maintain power on SAN Volume Controller nodes until data can be saved to the local hard-disk drive. Only SAN Volume Controller nodes can be plugged into the 2145
UPS-1U or the SAN Volume Controller clustered system will malfunction.
- Press and hold the on/off button ( 7 in Figure 6)
for approximately five seconds. You might need a pointed device, such
as a screwdriver, to press the on/off button. The front panel indicators
cycle through a startup sequence while the 2145
UPS-1U conducts
a self-test.
Figure 6. 2145
UPS-1U front-panel
assembly
When the self-test is complete, the power-on indicator 6 and the load indicators ( 1 and 2 ) illuminate to indicate that power is being supplied by the 2145
UPS-1U. The 2145
UPS-1U is now in normal mode, and is charging its battery. If the battery indicator 4 is on and the alarm is sounding, the voltage range setting might not be correct. When a SAN Volume Controller is connected to the 2145
UPS-1U, the SAN Volume Controller automatically adjusts the voltage range setting. Take no action for this alarm condition unless it persists for more than 5 minutes after a SAN Volume Controller is connected to this 2145
UPS-1U and turned on.
- Repeat all of these steps to install additional 2145
UPS-1U units.