SAS expansion enclosure environment requirements
Before you install a SAN Volume Controller 2145-12F, 2145-24F, 2145-92F, or 2147-92F SAS expansion enclosure, your physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Power requirements for each power supply (two per enclosure)
Ensure that your environment meets the following power requirements.
To aid in power and cooling requirements planning, Table 1 lists the rating of each power supply unit (PSU) by enclosure.
The power that is used by the system depends on several factors, including the number of enclosures and drives in the system and the ambient temperature.
| Model and type | PSU | Input power requirements | Maximum input current | Maximum power output | Caloric value (BTU/hr) |
|---|---|---|---|---|---|
2145-12F |
764 W (2) | 100 V to 240 V single phase AC at a frequency of 50 Hz to 60 Hz |
10A for 100V 6A for 240V |
764W | 2607 |
2145-92F |
2400 W (2) | 180 V to 264 V single phase AC at a frequency of 47 Hz to 63 Hz |
16A Requires a C19 power socket (C19 PDU) |
2400W | 8189 |
| Model and type | Configuration | Total power consumption |
|---|---|---|
| 2145-12F | 1 enclosure with 12 7.2 K RPM nearline SAS Drives | 175 W |
| 2145-24F | 1 enclosure with 24 2.5-inch flash drives | 151 W |
| 2145-24F | 1 enclosure with 24 10 K SAS drives | 175 W |
| 2145-24F | 1 enclosure with 24 15 K SAS drives | 234 W |
| 2145-24F | 1 enclosure with 12 7.2 K nearline SAS drives | 158 W |
| 2147-92F | 1 enclosure with 92 10 TB nearline SAS drives | 848 W |
| 2147-92F | 1 enclosure with 92 15 TB tier 1 flash drives | 748 W |
Each SAS expansion enclosure contains two PSUs for redundancy. The total power consumption values represent the total power that is drawn by both PSUs.
Environmental requirements
Ensure that your environment falls within the ranges that are shown in Table 3.
| Environment | Ambient temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating | 5°C to 35°C (5°C to 40°C for 12F/24F) 41°F to 95°F (41°F to 104°F for 12F/24F) |
0 - 2133 m (0 - 7000 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| 5°C to 30°C (41°F to 86°F) |
2134 - 3048 m (7001 - 10000 ft) |
|||
| Non-operating | 1°C to 50°C (34°F to 122°F) |
-305 to 12192 m (-1000 to 40000 ft) |
8% to 80% noncondensing | 27°C (80°F) |
| Storage | 1°C to 60°C (34°F to 140°F) |
5% to 80% noncondensing | 29°C (84°F) | |
| Shipping | -40°C to 60°C (-40°F to 140°F) |
5% to 100% condensing, but not precipitating |
Dimensions and weight
Ensure that space is available in a rack, capable of supporting the enclosure based on the data shown in Table 4.
| Enclosure | Height | Width | Depth | Maximum weight | |
|---|---|---|---|---|---|
| Drive ready (without drive modules) | Fully configured (with drive modules) | ||||
| 2145-12F | 87 mm (3.46 in.) | 483 mm (19.0 in.) | 556 mm (21.9 in.) | 16.4 kg (36.2 lb) | 26.7 kg (58.9 lb) |
| 2145-24F | 87 mm (3.46 in.) | 483 mm (19.0 in.) | 556 mm (21.9 in.) | 16.7 kg (36.8 lb) | 25.0 kg (55.1 lb) |
2145-92F |
222.2 mm (8.75 in.) | 483 mm (19.0 in.) | 968 mm (38.1 in.) | 67 kg (147.7 lb) | 135 kg (297 lb) |

Additional space requirements
Ensure that these additional space requirements, as shown in Table 5, are available around the enclosures.
| Location | Additional space requirements | Reason |
|---|---|---|
| Left and right sides | 50 mm (2 in.) |
Cooling air flow |
| Back | Minimum: 100 mm (4 in.) This is not needed for 92F models. |
Cable exit |
Supported drives for SAN Volume Controller SAS expansion enclosures
Table 6 provides drive specifications for SAN Volume Controller SAS expansion enclosures.
| Model and type | 3.5-inch drives | 2.5-inch drives |
|---|---|---|
| 2145-12F | 3.5” 7.2 K RPM 12 Gbps SAS nearline HDD 4 TB, 6 TB, 8 TB | - |
| 2145-24F | - |
|
2145-92F |
|
|
Acoustical specifications for SAN Volume Controller SAS expansion enclosures
The following table provides the acoustical specifications for the 2145-12F and 2145-24F SAS expansion enclosures.
| Model and type | Acoustical output per enclosure |
|---|---|
| 2145-12F | Less than 7.7 B LwA -- Operating (40% Average seek rate) @ 23°C ambient |
| 2145-24F | Less than 6.3 B LwA -- Operating (40% Average seek rate) @ 23°C ambient |
The noise emission level that is stated is the declared (upper limit) sound power level, in decibels, for a random sample of machines. All measurements are made in accordance with ISO 7779 and reported in conformance with ISO 9296.
Table 8 provides the acoustical specifications for the 2145-92F and 2147-92F SAS expansion enclosures in accordance with ISO 9296(1,2,3).
| Model and type | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idling | Operating | Idling | |
| Fully configured expansion enclosure, MTM/Model 2145-92F, 2147-92F | 8.5 | 8.5 | 85 | 85 |
Notes:
Important: Government regulations (such as those prescribed by OSHA or European
Community Directives) may govern noise level exposure in the workplace and may apply to you and your
server installation. This system is available with an optional acoustical door feature that can help
reduce the noise emitted from this system. The actual sound pressure levels in your installation
depend upon a variety of factors, including the number of racks in the installation; the size,
materials, and configuration of the room where you designate the racks to be installed; the noise
levels from other equipment; the room ambient temperature, and employees' location in relation to
the equipment. Further, compliance with such government regulations also depends upon a variety of
additional factors, including the duration of employees' exposure and whether employees wear hearing
protection. IBM® recommends that you consult with qualified
experts in this field to determine whether you are in compliance with the applicable
regulations.
|
||||
Shock and vibration specifications for SAN Volume Controller SAS expansion enclosures
Table 9 and Table 10 provide the shock and vibration testing results for SAN Volume Controller SAS expansion enclosures.
| Shock categories | Test level | Performance |
|---|---|---|
| Operational | 5 g 10 ms 1/2 Sine | <=25 g 10 ms |
| Non-operational | 30 g 10 ms 1/2 Sine | <=75 g 11 ms |
| Vibration categories | Test level | Performance |
|---|---|---|
| Operational | 0.21 grms 5-500Hz Random | Throughput loss <=10% FCAL <= 0.68 grms |
| Non-operational | 1.04 grms 2-200Hz Random | <=3.12 grms |
| Shipping | 0.3 g 2-200Hz Sine | <=5 g |
| Rotational vibration | Normal operation performance measurements in enclosure with no external vibration. | Throughput loss for all drives of the same type within performance profile. |