SAN Volume Controller 2145-CF8 environment requirements
Before you install a SAN Volume Controller 2145-CF8 node, your physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Input-voltage requirements
Ensure that your environment meets the voltage requirements that are shown in Table 1.
| Voltage | Frequency |
|---|---|
| 200 - 240 V single phase ac | 50 or 60 Hz |
- If the uninterruptible power supply is cascaded from another uninterruptible power supply, the source uninterruptible power supply must have at least three times the capacity per phase and the total harmonic distortion must be less than 5%.
- The uninterruptible power supply also must have input voltage capture that has a slew rate of no more than 3 Hz per second.
Power requirements for each node
Ensure that your environment meets the following power requirements.
Ensure that your environment meets the power requirements as shown in Table 2.
| Components | Power requirements |
|---|---|
| SAN Volume Controller 2145-CF8 node and 2145 UPS-1U power supply | 200 W |
- SAN Volume Controller 2145-CF8 nodes cannot connect to all revisions of the 2145 UPS-1U power supply unit. The SAN Volume Controller 2145-CF8 nodes require the 2145 UPS-1U power supply unit part number 31P1318. This unit has two power outlets that are accessible. Earlier revisions of the 2145 UPS-1U power supply unit have only one power outlet that is accessible and are not suitable.
For each redundant AC-power switch, add 20 W to the power requirements.
- For each high-speed SAS adapter with one to four flash drives, add 50 W to the power requirements.
Circuit breaker requirements
The 2145 UPS-1U has an integrated circuit breaker and does not require additional protection.
Environment requirements without redundant AC power
If you are not using redundant ac power, ensure that your environment falls within the ranges that are shown in Table 3.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 10°C to 35°C (50°F to 95°F) |
0 - 914 m (0 - 2998 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| Operating in higher altitudes | 10°C to 32°C (50°F to 90°F) |
914 - 2133 m (2998 - 6988 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| Turned off | 10°C to 43°C (50°F to 110°F) |
0 - 2133 m (0 - 6988 ft) |
8% to 80% noncondensing | 27°C (81°F) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 - 2133 m (0 - 6988 ft) |
5% to 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 - 10668 m (0 - 34991 ft) |
5% to 100% condensing, but no precipitation | 29°C (84°F) |
Environment requirements with redundant AC power
If you are using redundant ac power, ensure that your environment falls within the ranges that are shown in Table 4.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 15°C to 32°C (59°F to 90°F) |
0 - 914 m (0 - 2998 ft) |
20% to 80% noncondensing | 23°C (73°F) |
| Operating in higher altitudes | 15°C to 32°C (59°F to 90°F) |
914 - 2133 m (2998 - 6988 ft) |
20% to 80% noncondensing | 23°C (73°F) |
| Turned off | 10°C to 43°C (50°F to 110°F) |
0 - 2133 m (0 - 6988 ft) |
20% to 80% noncondensing | 27°C (81°F) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 - 2133 m (0 - 6988 ft) |
5% to 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 - 10668 m (0 - 34991 ft) |
5% to 100% condensing, but no precipitation | 29°C (84°F) |
Preparing your environment
The following tables list the physical characteristics of the SAN Volume Controller 2145-CF8 node.
Dimensions and weight
Use the parameters that are shown in Table 5 to ensure that space is available in a rack capable of supporting the node.
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
43 mm |
440 mm |
686 mm |
12.7 kg |
Additional space requirements
Ensure that space is available in the rack for the additional space requirements around the node, as shown in Table 6.
| Location | Additional space |
Reason |
|---|---|---|
| Left and right sides | 50 mm (2 in.) |
Cooling air flow |
| Back | Minimum: |
Cable exit |
Heat output of each SAN Volume Controller 2145-CF8 node
The node dissipates the maximum heat output that is given in Table 7.
| Model | Heat output per node |
|---|---|
| SAN Volume Controller 2145-CF8 | 160 W (546 Btu per hour) |
| SAN Volume Controller 2145-CF8 and up to four optional flash drives | 210 W (717 Btu per hour) |
| Maximum heat output of 2145 UPS-1U during typical operation | 10 W (34 Btu per hour) |
| Maximum heat output of 2145 UPS-1U during battery operation | 100 W (341 Btu per hour) |