SAN Volume Controller 2145-CG8 environment requirements
Before the SAN Volume Controller 2145-CG8 is installed, the physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Input-voltage requirements
Ensure that your environment meets the voltage requirements that are shown in Table 1.
| Voltage | Frequency |
|---|---|
| 200 V - 240 V single phase ac | 50 Hz or 60 Hz |
- If the uninterruptible power supply is cascaded from another uninterruptible power supply, the source uninterruptible power supply must have at least three times the capacity per phase and the total harmonic distortion must be less than 5%.
- The uninterruptible power supply also must have input voltage capture that has a slew rate of no more than 3 Hz per second.
Maximum power requirements for each node
Ensure that your environment meets the power requirements as shown in Table 2.
The maximum power that is required depends on the node type and the optional features that are installed.
| Components | Power requirements |
|---|---|
| SAN Volume Controller 2145-CG8 and 2145 UPS-1U | 200 W |
For each redundant AC-power switch, add 20 W to the power requirements.
For the high-speed SAS adapter with from one to four solid-state drives, add 50 W to the power requirements.
Circuit breaker requirements
The 2145 UPS-1U has an integrated circuit breaker and does not require additional protection.
Environment requirements without redundant AC power
If you are not using redundant ac power, ensure that your environment falls within the ranges that are shown in Table 3.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 10°C - 35°C (50°F - 95°F) |
0 m - 914 m (0 ft - 3000 ft) |
8% - 80% noncondensing | 23°C (73°F) |
| Operating in higher altitudes | 10°C - 32°C (50°F - 90°F) |
914 m - 2133 m (3000 ft - 7000 ft) |
8% - 80% noncondensing | 23°C (73°F) |
| Turned off | 10°C - 43°C (50°F - 109°F) |
0 m - 2133 m (0 ft - 7000 ft) |
8% - 80% noncondensing | 27°C (81°F) |
| Storing | 1°C - 60°C (34°F - 140°F) |
0 m - 2133 m (0 ft - 7000 ft) |
5% - 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C - 60°C (-4°F - 140°F) |
0 m - 10668 m (0 ft - 34991 ft) |
5% - 100% condensing, but no precipitation | 29°C (84°F) |
Environment requirements with redundant AC power
If you are using redundant ac power, ensure that your environment falls within the ranges that are shown in Table 4.
| Environment | Temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating in lower altitudes | 15°C - 32°C (59°F - 90°F) |
0 m - 914 m (0 ft - 3000 ft) |
20% - 80% noncondensing | 23°C (73°F) |
| Operating in higher altitudes | 15°C - 32°C (59°F - 90°F) |
914 m - 2133 m (3000 ft - 7000 ft) |
20% - 80% noncondensing | 23°C (73°F) |
| Turned off | 10°C - 43°C (50°F - 109°F) |
0 m - 2133 m (0 ft - 7000 ft) |
20% - 80% noncondensing | 27°C (81°F) |
| Storing | 1°C - 60°C (34°F - 140°F) |
0 m - 2133 m (0 ft - 7000 ft) |
5% - 80% noncondensing | 29°C (84°F) |
| Shipping | -20°C - 60°C (-4°F - 140°F) |
0 m - 10668 m (0 ft - 34991 ft) |
5% - 100% condensing, but no precipitation | 29°C (84°F) |
Preparing your environment
The following tables list the physical characteristics of the SAN Volume Controller 2145-CG8 node.
Dimensions and weight
Use the parameters that are shown in Table 5 to ensure that space is available in a rack capable of supporting the node.
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
4.3 cm |
44 cm |
73.7 cm |
15 kg |
Additional space requirements
Ensure that space is available in the rack for the additional space requirements around the node, as shown in Table 6.
| Location | Additional space requirements | Reason |
|---|---|---|
| Left side and right side | Minimum: 50 mm (2 in.) | Cooling air flow |
| Back | Minimum: 100 mm (4 in.) | Cable exit |
Maximum heat output of each SAN Volume Controller 2145-CG8 node
The node dissipates the maximum heat output that is given in Table 7.
| Model | Heat output per node |
|---|---|
| SAN Volume Controller 2145-CG8 | 160 W (546 Btu per hour) |
| SAN Volume Controller 2145-CG8 plus flash drive | 210 W (717 Btu per hour) |
Maximum heat output of each 2145 UPS-1U
The 2145 UPS-1U dissipates the maximum heat output that is given in Table 8.
| Model | Heat output per node |
|---|---|
| Maximum heat output of 2145 UPS-1U during normal operation | 10 W (34 Btu per hour) |
| Maximum heat output of 2145 UPS-1U during battery operation | 100 W (341 Btu per hour) |