MAP 5320: Redundant AC power helps you solve problems that have occurred in the redundant AC-power
switches used on the system. Use
this MAP when a 2145 UPS-1U that is
connected to a redundant AC-power
switch does not
appear to have input power.
Before you begin
If you are not familiar with these maintenance analysis
procedures (MAPs), first read Using the maintenance analysis procedures.
You
might have been sent here for one of the following reasons:
About this task
Perform the following steps to solve problems that have
occurred in any redundant AC-power
switch:
Procedure
- One or two 2145
UPS-1Us
might be connected to the redundant AC-power
switch. Is
the power-on indicator on any connected 2145
UPS-1U on?
- NO
- Go to step 3.
- YES
- The redundant AC-power
switch is
powered. Go to step 2.
- (from step 1)
Measure
the voltage at the redundant AC-power
switch output
socket connected to the 2145
UPS-1U that
is not showing power-on.
CAUTION:
Ensure that you do
not remove the power cable of any powered uninterruptible power
supply units
Is
there power at the output socket?- NO
- One redundant AC-power
switch output
is working while the other is not. Replace the redundant AC-power
switch.
CAUTION:
- YES
- The redundant AC-power
switch is
working. There is a problem with the 2145
UPS-1U power
cord or the 2145
UPS-1U .
Return to the procedure that called this MAP and continue from where
you were within that procedure. It will help you analyze the problem
with the 2145
UPS-1U power
cord or the 2145
UPS-1U.
- (from step 1)
None
of the used redundant AC-power
switch outputs
appears to have power.
Are the two input power cables for
the redundant AC-power
switches correctly
connected to the redundant AC-power
switch and
to different mains circuits?- NO
- Correctly connect the cables. Go to MAP 5340: Redundant AC power verification.
- YES
- Verify that there is main power at both the site's power
distribution units that are providing power to this redundant AC-power
switch.
Go to step 4.
- (from step 3)
Is
power available at one or more of the site's power distribution
units that are providing power to this
redundant AC-power
switch?
- NO
- Have the customer fix the mains circuits. Return to the procedure
that called this MAP and continue from where you were within that
procedure.
- YES
- The redundant AC-power
switch should
operate in this situation. Replace the redundant AC-power
switch assembly.
After you replace the redundant AC-power
switch,
continue with MAP 5340: Redundant AC power verification.