Follow all safety notices when you are removing the 2145
UPS battery.
Before you begin
DANGER
Uninterruptible power
supply
(UPS) units contain specific hazardous materials. Observe the following precautions if your product
contains a UPS:
- The UPS contains lethal voltages. All repairs and service must be performed only by an
authorized service support representative. There are no user serviceable parts inside the UPS.
- The UPS contains its own energy source (batteries). The output receptacles might carry live
voltage even when the UPS is not connected to an AC supply.
- Do not remove or unplug the input cord when the UPS is turned on. This removes the safety ground
from the UPS and the equipment connected to the UPS.
- The UPS is heavy because of the electronics and batteries that are required. To avoid injury,
observe the following precautions:
- Do not attempt to lift the UPS by yourself. Ask another service representative for
assistance.
- Remove the battery, electronics assembly, or both from the UPS before removing the UPS from the
shipping carton or installing or removing the UPS in the rack. (D007)
CAUTION:
The weight of this part or unit is between 32 and 55 kg (70.5 and 121.2 lb). It takes
three persons to safely lift this part or unit. (C010)
Use the reference numbers in parentheses at the end of each notice (for example,
D005) to find the matching translated notice in IBM System Storage SAN Volume Controller Safety Notices.
About this task
Important: Before you perform step 1, check to
make sure that any
SAN Volume Controller that
is powered by this
2145 UPS is
shut down and turned off. See
MAP 5350: Powering off a node.
Perform
the following steps to remove the 2145 UPS battery
assembly:
Procedure
- At the front of the 2145 UPS,
press and hold the off button ( 1 in Figure 1)
for approximately five seconds or until the long beep stops.
Figure 1. 2145 UPS front-panel
assembly
- Remove the front panel by pressing the sides inward, and
pulling on both ends towards you, as shown in Figure 2.
Figure 2. Removing the 2145 UPS front
panel
- Perform the following steps to remove the battery retaining
bracket, which is shown in Figure 3:
- Remove the two bolts 1 .
- Remove the hex nut 2 .
- Remove the battery retaining bracket 3 .
Figure 3. Fastening
the battery retaining bracket
- Remove the battery plate to access to the battery, as shown
in Figure 4.
Figure 4. Removing the 2145 UPS battery
- Grab the tabs on the battery assembly and pull the battery
outward to allow two people to access it for removal.
- With the help from another service support
representative, pull the battery out onto a flat, stable surface.