Follow all safety notices when you are replacing the 2145
UPS battery.
Before you begin
DANGER
Uninterruptible power
supply
(UPS) units contain specific hazardous materials. Observe the following precautions if your product
contains a UPS:
- The UPS contains lethal voltages. All repairs and service must be performed only by an
authorized service support representative. There are no user serviceable parts inside the UPS.
- The UPS contains its own energy source (batteries). The output receptacles might carry live
voltage even when the UPS is not connected to an AC supply.
- Do not remove or unplug the input cord when the UPS is turned on. This removes the safety ground
from the UPS and the equipment connected to the UPS.
- The UPS is heavy because of the electronics and batteries that are required. To avoid injury,
observe the following precautions:
- Do not attempt to lift the UPS by yourself. Ask another service representative for
assistance.
- Remove the battery, electronics assembly, or both from the UPS before removing the UPS from the
shipping carton or installing or removing the UPS in the rack. (D007)
CAUTION:
Lead-acid batteries can present a risk of electrical burn from high,
short-circuit current. Avoid battery contact with metal materials; remove watches, rings, or other
metal objects, and use tools with insulated handles. To avoid possible explosion, do not burn.
(C004)
Use the reference numbers in parentheses at the end of each notice (for example,
D005) to find the matching translated notice in IBM System Storage SAN Volume Controller Safety Notices.
About this task
Perform the following
steps to replace the 2145 UPS battery
assembly:
Procedure
- Make sure that the 2145 UPS is
powered off and unplugged.
- With the help from another service support representative,
grab the tabs on the battery assembly and gently push the battery
in to the 2145 UPS.
- Replace the battery plate, as shown in Figure 1.
Figure 1. Replacing the 2145 UPS battery
plate
- Perform the following steps to replace the battery retaining
bracket:
- Replace the battery retaining bracket ( 3 in Figure 2).
- Replace the hex nut 2 .
- Replace the two bolts 1 .
Figure 2. Fastening
the battery retaining bracket
- If the battery has two red cables that are disconnected,
perform the following steps to connect the internal battery connector:
- Remove the protective tape from the internal battery
connector (shown in Figure 3).
Figure 3. The 2145 UPS internal
battery connector with protective tape
- Connect the internal battery connector (shown in Figure 4).
Note: A
small amount of arcing might occur when connecting the batteries.
This is normal and does not damage the unit or present any safety
concerns.
Figure 4. Connecting
the 2145 UPS internal
battery connectors
- Replace the front panel by pressing the sides inward, and
pushing on both ends towards the 2145 UPS,
as shown in Figure 5).
Figure 5. Replacing the 2145 UPS front
panel
- At the front of the 2145 UPS,
press and hold the on button until you hear a beep (approximately
one second). The mode indicator stops flashing, and the load-level
indicators display the percentage of load that is being applied to
the 2145 UPS.
See 2145 UPS controls and indicators for
more information.