Contamination information
Contamination information that pertains to the system is included in this topic.
Airborne particulates (including metal flakes or particles) and reactive gases, acting alone or in combination with other environmental factors such as humidity or temperature, might pose a risk to the system hardware. Risks that are posed by the presence of excessive particulate levels or concentrations of harmful gases include damage that might cause the system hardware to malfunction or cease functioning altogether. This specification specifies limits for particulates and gases that are intended to avoid such damage. The limits must not be viewed or used as definitive limits because numerous other factors, such as temperature or moisture content of the air, can influence the impact of particulates or environmental corrosives and gaseous contaminant transfer.
In the absence of specific limits that are specified in this document, you must implement practices that maintain particulate or gas levels that are consistent with the protection of human health and safety. If IBM determines that the levels of particulates or gases in your environment caused damage to the system hardware, IBM might require remedial measures to mitigate such environmental contamination. Implementation of appropriate remedial measures might be necessary before IBM provides repair or replacement of the system hardware. Implementation of such remedial measures is a customer responsibility.
- Severity level G1 as per ANSI/ISA 71.04-19851, which states that the reactivity rate of copper coupons shall be less than 300 Angstroms per month (Å/month, ≈ 0.0039 μg/cm2-hour weight gain)2. In addition, the reactivity rate of silver coupons shall be less than 300Å/month (≈ 0.0035 μg/cm2-hour weight gain)3. The reactive monitoring of gaseous corrosivity should be conducted approximately 2 inches (5 cm) in front of the rack on the air inlet side at one-quarter and three-quarter frame height off the floor, or where the air velocity is much higher.
- Data centers must meet the cleanliness level of ISO 14644-1 class 8. For data centers without
airside economizers, the ISO 14644-1 class 8 cleanliness can be met by choosing one of the following
filtration methods: