Before you begin to remove the 2145 UPS
,
read all safety notices.
Before you begin
Use the reference numbers in parentheses at the end of each notice (for example,
D005) to find the matching translated notice in IBM System Storage SAN Volume Controller Safety Notices.
DANGER
Uninterruptible power supply
(UPS) units contain specific hazardous materials. Observe the following precautions if your product
contains a UPS:
- The UPS contains lethal voltages. All repairs and service must be performed only by an
authorized service support representative. There are no user serviceable parts inside the UPS.
- The UPS contains its own energy source (batteries). The output receptacles might carry live
voltage even when the UPS is not connected to an AC supply.
- Do not remove or unplug the input cord when the UPS is turned on. This removes the safety ground
from the UPS and the equipment connected to the UPS.
- The UPS is heavy because of the electronics and batteries that are required. To avoid injury,
observe the following precautions:
- Do not attempt to lift the UPS by yourself. Ask another service representative for
assistance.
- Remove the battery, electronics assembly, or both from the UPS before removing the UPS from the
shipping carton or installing or removing the UPS in the rack. (D007)
CAUTION:
The weight of this part or unit is between 32 and 55 kg (70.5 and 121.2 lb). It takes
three persons to safely lift this part or unit. (C010)
About this task
Perform the following steps to remove the 2145 UPS
:
Attention: Check to make sure that any
SAN Volume Controller
that
is powered by this
2145 UPS
is
shut down and turned off, prior to step 1. See
MAP 5350: Powering off a node.
Procedure
- At the front of the 2145 UPS
,
press and hold the off button (
in Figure 1)
for approximately five seconds or until the long beep stops. Figure 1. 2145 UPS
front-panel
assembly
- At
the back of the 2145 UPS
(Figure 2), disconnect
the
power cables of the SAN Volume Controller
.
- Disconnect the signal cables (
in Figure 2).
- Disconnect the main power cable (
in Figure 2). Figure 2. 2145 UPS
connectors and circuit breakers
- Remove
the battery from the 2145 UPS
.
See Removing the 2145 UPS battery.
- Remove the electronics assembly from the 2145 UPS
.
See Removing the 2145 UPS electronics.
- At the front of the 2145 UPS
,
unscrew the mounting screws (
in Figure 3). Figure 3. Removing the 2145 UPS
- At
the back of the rack, push the 2145 UPS
forward
approximately 5 cm (2 in) to enable you to pull it from the rack.
- Go to the front of the rack.
- With
aid from another service representative, pull the 2145 UPS
forward
and remove it from the rack.
- Replace the 2145 UPS
.
See Replacing the 2145 UPS.