You can replace the air baffle on a SAN Volume Controller 2145-SV1 node.
Before you begin
DANGER
Multiple power cords. The product might be equipped with multiple
power cords. To remove all hazardous voltages, disconnect all power cords. (L003)
Take precautions to avoid damage from static electricity. Wear an anti-static wrist strap and use
a static-protected mat or surface.
About this task
This service action assumes:
- You are not operating the 2145-SV1 node without the air
baffle.
- The node is turned off. If you must turn off the node, ensure that hosts
will not lose access to data in volumes, as described in MAP 5350: Powering off a node.
- The power cables are disconnected.
- The top back cover is removed.
To replace the air baffle, complete the following steps.
Procedure
- Read the safety information.
- Hold the air baffle at a slight angle to align it within the sides of the chassis, as shown in
Figure 1.
Figure 1. Aligning the air baffle
- Lower the air baffle into place; make sure that all cables are out of the way.
- Press the air baffle down until it is securely seated, as shown in Figure 2.
Figure 2. Replacing the air baffle
- Replace the top back cover, as described in Replacing the top covers: 2145-SV1.
- If you removed the node from the rack, replace it, as described in Replacing a node in a rack: 2145-SV1.
- If you removed any Fibre Channel or Ethernet cables, reconnect them to the same ports from
which they were removed.
- Reconnect the power cords. The node powers on when the cords are reconnected.