Use this topic when you need to remove a redundant AC-power switch on a SAN Volume Controller 2145-CG8 or
2145-CF8 node.
Before you begin
DANGER
Multiple power cords. The product might be equipped with multiple
power cords. To remove all hazardous voltages, disconnect all power cords. (L003)
Use the reference numbers in parentheses at the end of each notice (for example,
D005) to find the matching translated notice in IBM System Storage SAN Volume Controller Safety Notices.
About this task
Note: The following procedure is applicable only for 2145-CG8 or 2145-CF8 nodes.
To remove a
redundant AC-power switch, complete the following
steps.
Procedure
- Turn off each SAN Volume Controller
node
that is connected by an uninterruptible power supply to
the redundant AC-power switch.
See MAP 5350: Powering off a node.
- One or two nodes might be connected to the redundant AC-power switch. If two nodes are connected to
the redundant AC-power switch, you must ensure that
both nodes are not in the same I/O group before you turn off the nodes. If the nodes are both turned
off and they are in the same I/O group, the customer loses access to the data that is managed by
that I/O group.
- If both nodes that are powered by the redundant AC-power switch are in the same I/O group, turn
off one node, disconnect it from the redundant AC-power switch, and connect it to a different
power source. Then, turn the node back on. When it recovers and rejoins the I/O group, it can
maintain the I/O access when the other node is turned off and when the redundant AC-power switch is removed. When you perform this
operation, pay particular attention to checking when it is safe to turn off the second node. See
MAP 5350: Powering off a node.
- Remove both the redundant AC-power switch
input-power cables from the site power distribution unit and unthread them in the rack, so they
slide out when the redundant AC-power switch is
removed. There might be enough access to disconnect them from the redundant AC-power switch while it is in the rack, but
often it is more convenient to leave them attached and remove them with the redundant AC-power switch.
- Remove the one or two redundant AC-power switches to 2145 UPS-1U
power
cables from the redundant AC-power switch.
There is no need to disconnect them from the 2145 UPS-1U
.
- Remove the four screws that hold the redundant AC-power switch in
the rack. Be careful to support the redundant AC-power switch during
this procedure because the screws are the only support for the unit.
- The redundant AC-power switch can
be slid out of the rack along with the input-power cables if
they are still attached.