1089 Service Processor shows fan failure

Explanation

One or more fans are failing.

For the 2145-DH8 , a fan has a fault condition.

User response

  1. Determine the failing fans from the fan indicator on the system board or from the text of the error data in the log. Each fan module contains two fans.
  2. For the 2145-DH8 , mechanically stop fan or remove fan. If a fan is not installed, shut down the node, open it, and install the fan. If a fan is installed, replace fan FRU indicated by the FAN identifier that is supplied in the Extra data.
  3. Exchange the FRU for a new FRU.
  4. Go to repair verification MAP.
  • Fan number: Fan module position
  • 1 or 2 :1
  • 3 or 4 :2
  • 5 or 6 :3
  • 7 or 8 :4
  • 9 or 10:5
  • 11 or 12:6

Possible Cause-FRUs or other:

  • Fan module (100%)