SAN Volume Controller 2145-DH8 environment requirements
Before the SAN Volume Controller 2145-DH8 is installed, the physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Input-voltage requirements
Ensure that your environment meets the voltage requirements that are shown in Table 1.
| Voltage | Frequency |
|---|---|
| 100-127 / 200-240Vac | 50 Hz or 60 Hz |
Maximum power requirements for each node
Ensure that your environment meets the power requirements as shown in Table 2.
The maximum power that is required depends on the node type and the optional features that are installed.
| Components | Power requirements |
|---|---|
| SAN Volume Controller 2145-DH8 | 200 W typical, 750 W maximum (200 - 240V ac, 50/60 Hz) |
Environment requirements without redundant AC power
Ensure that your environment falls within the following ranges if you are not using redundant AC power.
| Environment | Temperature | Altitude | Relative humidity | Maximum dew point |
|---|---|---|---|---|
| Operating in lower altitudes | 5°C to 40°C (41°F to 104°F) |
0 to 950 m (0 ft to 3,117 ft) |
8% to 85% | 24°C (75°F) |
| Operating in higher altitudes | 5°C to 28°C (41°F to 82°F) |
951 m to 3,050 m (3,118 ft to 10,000 ft) |
||
| Turned off (with standby power) | 5°C to 45°C (41°F to 113°F) |
0 m to 3,050 m (0 ft to 10,000 ft) |
8% to 85% | 27°C (80.6°F) |
| Storing | 1°C to 60°C (33.8°F to 140.0°F) |
0 m to 3,050 m (0 ft to 10,000 ft) |
5% to 80% | 29°C (84.2°F) |
| Shipping | -40°C to 60°C (-40°F to 140.0°F) |
0 m to 10,700 m (0 ft to 34,991 ft) |
5% to 100% | 29°C (84.2°F) |
Preparing your environment
The following tables list the physical characteristics of the 2145-DH8 node.
Dimensions and weight
Use the parameters that are shown in Table 4 to ensure that space is available in a rack capable of supporting the node.
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
| 86 mm (3.4 in.) | 445 mm (17.5 in) | 746 mm (29.4 in) | 25 kg (55 lb) to 30 kg (65 lb) depending on configuration |
Additional space requirements
Ensure that space is available in the rack for the additional space requirements around the node, as shown in Table 5.
| Location | Additional space requirements | Reason |
|---|---|---|
| Left side and right side | Minimum: 50 mm (2 in.) | Cooling air flow |
| Back | Minimum: 100 mm (4 in.) | Cable exit |
Maximum heat output of each 2145-DH8 node
The node dissipates the maximum heat output that is given in Table 6.
| Model | Heat output per node |
|---|---|
| 2145-DH8 |
|