SAS expansion enclosure environment requirements
Before you install a 2U or a 5U SAS expansion enclosure, your physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met. (SAS expansion enclosures are not supported by SAN Volume Controller 2145-SV2 or 2145-SA2 nodes.)
Power requirements for each power supply (two per enclosure)
Ensure that your environment meets the following power requirements.
The power that is used by the system depends on several factors, including the number of enclosures and drives in the system and the ambient temperature.
| Model and type | PSU | Input power requirements | Maximum input current | Maximum power output | Caloric value (BTU/hr) |
|---|---|---|---|---|---|
|
2145-12F 2145-24F |
764 W (2) |
100 V to 240 V single phase AC at a frequency of 50 Hz to 60 Hz |
10A for 100V 6A for 240V |
764W | 2607 |
|
2145-92F , 2147-92F |
2400 W (2) |
AC 200-240 V~ ,
(nominal; +/- 10% tolerant)
50/60 Hz
(nominal; 47-63 Hz tolerant) |
12 A (x2 - per inlet redundancy) Requires an IEC C20 appliance coupler (16-20A branch circuit or C19 power socket PDU) |
2400W | 8189 |
| Model and type | Configuration | Total power consumption |
|---|---|---|
| 2145-12F | 1 enclosure with 12 7.2 K RPM nearline SAS Drives | 175 W |
| 2145-24F | 1 enclosure with 24 2.5-inch flash drives | 151 W |
| 2145-24F | 1 enclosure with 24 10 K SAS drives | 175 W |
| 2145-24F | 1 enclosure with 24 15 K SAS drives | 234 W |
| 2145-24F | 1 enclosure with 12 7.2 K nearline SAS drives | 158 W |
| 2147-92F | 1 enclosure with 92 10 TB nearline SAS drives | 848 W |
| 2147-92F | 1 enclosure with 92 15 TB tier 1 flash drives | 748 W |
Each SAS expansion enclosure contains two PSUs for redundancy. The total power consumption values represent the total power that is drawn by both PSUs.
Environmental requirements
| Environment | Ambient temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating | 5°C to 35°C (5°C to 40°C for 12F/24F)
41°F to 95°F (41°F to 104°F for 12F/24F) |
0 - 2133 m (0 - 7000 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| 5°C to 30°C (41°F to 86°F) |
2134 - 3048 m (7001 - 10000 ft) |
|||
| Non-operating | 1°C to 50°C (34°F to 122°F) |
-305 to 12192 m
(-1000 to 40000 ft) |
8% to 80% noncondensing | 27°C (80°F) |
| Storage | 1°C to 60°C (34°F to 140°F) |
5% to 80% noncondensing | 29°C (84°F) | |
| Shipping | -40°C to 60°C (-40°F to 140°F) |
5% to 100% condensing, but not precipitating |
Dimensions and weight
| Enclosure | Height | Width | Depth | Maximum weight | |
|---|---|---|---|---|---|
| Drive ready (without drive modules) | Fully configured (with drive modules) | ||||
| 2145-12F | 87 mm (3.46 in.) | 483 mm (19.0 in.) | 556 mm (21.9 in.) | 16.4 kg (36.2 lb) | 26.7 kg (58.9 lb) |
| 2145-24F | 87 mm (3.46 in.) | 483 mm (19.0 in.) | 556 mm (21.9 in.) | 16.7 kg (36.8 lb) | 25.0 kg (55.1 lb) |
|
2145-92F , 2147-92F |
222.2 mm (8.75 in.) | 483 mm (19.0 in.) | 968 mm (38.1 in.) | 67 kg (147.7 lb) | 135 kg (297 lb) |
- When you are powering off a 92F, 92G, or an A9F 5U expansion enclosure because you intend to transport it to another location
- When you intend to move a rack that contains a 92F, 92G, or an A9F 5U expansion enclosure

Additional space requirements
| Location | Additional space requirements | Reason |
|---|---|---|
| Left and right sides |
50 mm (2 in.)
|
Cooling air flow |
| Back | Minimum: 100 mm (4 in.)
This is not needed for 92F
models. |
Cable exit |
Supported drives for SAS expansion enclosures
| Model and type | 3.5-inch drives | 2.5-inch drives |
|---|---|---|
| 2145-12F | 3.5” 7.2 K RPM 12 Gbps SAS nearline HDD 4 TB, 6 TB, 8 TB | - |
| 2145-24F | - |
|
|
2145-92F , 2147-92F |
|
|
Acoustical specifications for SAS expansion enclosures
The following table provides the acoustical specifications for the 2U SAS expansion enclosures.
| Model and type | Acoustical output per enclosure |
|---|---|
| 2145-12F | Less than 7.7 B LwA -- Operating (40% Average seek rate) @ 23°C ambient |
| 2145-24F | Less than 6.3 B LwA -- Operating (40% Average seek rate) @ 23°C ambient |
The noise emission level that is stated is the declared (upper limit) sound power level, in decibels, for a random sample of machines. All measurements are made in accordance with ISO 7779 and reported in conformance with ISO 9296.
| Model and type | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idling | Operating | Idling | |
| Fully configured expansion enclosure, MTM/Model 2145-92F , , 2147-92F | 8.5 | 8.5 | 85 | 85 |
|
Notes:
Important: Government regulations (such as those prescribed by OSHA or European
Community Directives) may govern noise level exposure in the workplace and may apply to you and your
server installation. This system is available with an optional acoustical door feature that can help
reduce the noise emitted from this system. The actual sound pressure levels in your installation
depend upon a variety of factors, including the number of racks in the installation; the size,
materials, and configuration of the room where you designate the racks to be installed; the noise
levels from other equipment; the room ambient temperature, and employees' location in relation to
the equipment. Further, compliance with such government regulations also depends upon a variety of
additional factors, including the duration of employees' exposure and whether employees wear hearing
protection. IBM® recommends that you consult with qualified
experts in this field to determine whether you are in compliance with the applicable
regulations.
|
||||
Shock and vibration specifications for SAS expansion enclosures
| Shock categories | Test level | Performance |
|---|---|---|
| Operational | 5 g 10 ms 1/2 Sine | <=25 g 10 ms |
| Non-operational | 30 g 10 ms 1/2 Sine | <=75 g 11 ms |
| Vibration categories | Test level | Performance |
|---|---|---|
| Operational | 0.21 grms 5-500Hz Random | Throughput loss <=10% FCAL <= 0.68 grms |
| Non-operational | 1.04 grms 2-200Hz Random | <=3.12 grms |
| Shipping | 0.3 g 2-200Hz Sine | <=5 g |
| Rotational vibration | Normal operation performance measurements in enclosure with no external vibration. | Throughput loss for all drives of the same type within performance profile. |