SAN Volume Controller 2145-SV2 and 2145-SA2 environment requirements
Before the node is installed, the physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Input-voltage requirements
Ensure that your environment meets the voltage requirements that are shown in Table 1.
| Voltage | Frequency |
|---|---|
| 200-240 V AC | 50 Hz or 60 Hz |
Power requirements for each node
Ensure that your environment meets the typical power requirement as shown in Table 2.
| Component | Power requirements |
|---|---|
| SAN Volume Controller 2145-SV2 | 530 W in typical configuration (384 GB of memory and three 4 port 32 Gbps FC adapters) (200 - 240V AC, 50/60 Hz) |
| 2145-SA2 | 326 W in typical configuration (384 GB of memory and three 4 port 32 Gbps FC adapters) (200 - 240V AC, 50/60 Hz) |
Environment requirements without redundant AC power
Ensure that your environment falls within the following ranges if you are not using redundant AC power.
| Environment | Temperature | Altitude | Relative humidity | Maximum dew point |
|---|---|---|---|---|
| Operating in lower altitudes | 5°C to 40°C (41°F to 104°F) |
0 - 950 m (0 ft to 3,117 ft) |
8% to 85% | 24°C (75°F) |
| Operating in higher altitudes | 5°C to 28°C (41°F to 82°F) |
951 m to 3,050 m (3,118 ft to 10,000 ft) |
||
| Turned off (with standby power) | 5°C to 45°C (41°F to 113°F) |
0 m to 3,050 m (0 ft to 10,000 ft) |
8% to 85% | 27°C (80.6°F) |
| Storing | 1°C to 60°C (33.8°F to 140.0°F) |
0 m to 3,050 m (0 ft to 10,000 ft) |
5% to 80% | 29°C (84.2°F) |
| Shipping | -40°C to 60°C (-40°F to 140.0°F) |
0 m to 10,700 m (0 ft to 34,991 ft) |
5% to 100% | 29°C (84.2°F) |
Preparing your environment
The following tables list the physical characteristics of a SAN Volume Controller 2145-SV2 node.
Dimensions and weight
Use the parameters that are shown in Table 4 to ensure that space is available in a rack capable of supporting the node.
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
| 87 mm (3.4 in.) | 447 mm (17.6 in) | 746 mm (30.1 in) | 25 kg (55 lb) to 30 kg (65 lb) depending on configuration |
Additional space requirements
Ensure that space is available in the rack for the additional space requirements around the node, as shown in Table 5.
| Location | Additional space requirements | Reason |
|---|---|---|
| Left side and right side | Minimum: 50 mm (2 in.) | Cooling air flow |
| Back | Minimum: 100 mm (4 in.) If the cable-management arm is used, allow 177 mm (7 in.) |
Cable exit |
Maximum heat output of each SAN Volume Controller 2145-SV2 node
The node dissipates the maximum heat output that is given in Table 6.
| Model | Heat output per node |
|---|---|
| SAN Volume Controller 2145-SV2 | Typical configuration: 1808 BTU per hour (530 watts) |
| 2145-SA2 | Typical configuration: 1112 BTU per hour (326 watts) |
Acoustical declaration with noise hazard notice
| Product description | Declared A-weighted sound power level, LWA,m (B) | Declared A-weighted emission sound pressure level, LpA,m (dB) | Statistical adder for verification, Kv (B) | |||
|---|---|---|---|---|---|---|
| Operating | Idling | Operating | Idling | Operating | Idling | |
| Principal configuration: Single 2U enclosure in a rack; MTM 2145-SV2, 2145-SA2, 2147-SV2, and 2147-SA2; 25 degrees C | 7.8 | 7.8 | - | - | 0.3 | 0.3 |
| Maximum configuration: Single 2U enclosure in a rack; MTM 2145-SV2, 2145-SA2, 2147-SV2, and 2147-SA2; 27 degrees C | 8.1 | 8.1 | - | - | 0.3 | 0.3 |
| Maximum configuration: Single 2U enclosure in a rack; MTM 2145-SV2, 2145-SA2, 2147-SV2, and 2147-SA2; Maximum fan speeds | 9.0 | 9.0 | - | - | 0.3 | 0.3 |
| Maximum configuration: Single 2U enclosure in a rack; MTM 2145-SV2, 2145-SA2, 2147-SV2, and 2147-SA2; Maximum fan speeds, Service Position | - | - | 87 (7) | 87 (7) | 0.3 | 0.3 |
| Notes: |
||||||