Environmental requirements
Before you install a Storwize® V7000 Gen2 or Storwize V7000 Gen2+ system, your physical environment must meet certain requirements. This includes verifying that adequate space is available and that requirements for power and environmental conditions are met.
Safety notices
Use the following general safety information for all rack-mounted devices:
- Heavy equipment–personal injury or equipment damage might result if mishandled.
- Always lower the leveling pads on the rack cabinet.
- Always install stabilizer brackets on the rack cabinet.
- To avoid hazardous conditions due to uneven mechanical loading, always install the heaviest devices in the bottom of the rack cabinet. Always install servers and optional devices starting from the bottom of the rack cabinet.
- Rack-mounted devices are not to be used as shelves or work spaces. Do not place objects on
top of rack-mounted devices.

- Each rack cabinet might have more than one power cord. Be sure to disconnect all power cords in the rack cabinet when directed to disconnect power during servicing.
- Connect all devices installed in a rack cabinet to power devices installed in the same rack cabinet. Do not plug a power cord from a device installed in one rack cabinet into a power device installed in a different rack cabinet.
- An electrical outlet that is not correctly wired could place hazardous voltage on the metal parts of the system or the devices that attach to the system. It is the responsibility of the customer to ensure that the outlet is correctly wired and grounded to prevent an electrical shock. (R001 part 1 of 2)
- Do not install a unit in a rack where the internal rack ambient temperatures will exceed the manufacturer's recommended ambient temperature for all your rack-mounted devices.
- Do not install a unit in a rack where the air flow is compromised. Ensure that air flow is not blocked or reduced on any side, front, or back of a unit used for air flow through the unit.
- Consideration should be given to the connection of the equipment to the supply circuit so that overloading of the circuits does not compromise the supply wiring or overcurrent protection. To provide the correct power connection to a rack, refer to the rating labels located on the equipment in the rack to determine the total power requirement of the supply circuit.
- (For sliding drawers) Do not pull out or install any drawer or feature if the rack stabilizer brackets are not attached to the rack. Do not pull out more than one drawer at a time. The rack might become unstable if you pull out more than one drawer at a time.
- (For fixed drawers) This drawer is a fixed drawer and must not be moved for servicing unless specified by the manufacturer. Attempting to move the drawer partially or completely out of the rack might cause the rack to become unstable or cause the drawer to fall out of the rack. (R001 part 2 of 2)
Power requirements for each power supply
The power that is used by the system depends on various factors, including the number of enclosures and drives in the system and the ambient temperature. Ensure that your environment meets the following power requirements for each of the two power supply units (PSUs) in the enclosure.
Each control enclosure contains two PSUs for redundancy. The total power consumption values represent the total power that is drawn by both PSUs.
To aid in power and cooling requirements planning, Table 1 lists the rating of each power supply unit (PSU) by enclosure.
| Model and type | PSU | Input power requirements | Maximum input current | Maximum power output | Caloric value (BTU / hr) |
|---|---|---|---|---|---|
| 2076-524 / 2076-624 / 2076-U7A control enclosure with 24 2.5-inch solid-state drives, 2 host adapters, 2 compression accelerators | 1200 W | 100 V to 240 V single phase AC At a frequency of 50 Hz or 60 Hz |
12 A for 100 V 7 A for 240 V |
452 W | 1542 |
| 2076-524 / 2076-624 / 2076-U7A control enclosure with 24 10 K SAS Drives, 2 host adapters, 2 compression accelerators | 1200 W | 100 V to 240 V single phase AC At a frequency of 50 Hz or 60 Hz |
12 A for 100 V 7 A for 240 V |
430 W | 1467 |
| 2076-524 / 2076-624 / 2076-U7A control enclosure with 24 15 K SAS drives, 2 host adapters, 2 compression accelerators | 1200 W | 100 V to 240 V single phase AC At a frequency of 50 Hz or 60 Hz |
12 A for 100 V 7 A for 240 V |
471 W | 1607 |
| 5U Expansion enclosure with 92 3.5-inch form factor SAS drive slots | 2400 W | 180 V to 264 V single phase AC at a frequency of 47 Hz to 63 Hz | 16 A Requires a C19 power socket (C19 PDU) |
2400 W | 8189 |
| Model and type | Configuration | Total power consumption | Caloric value (BTU/hr) |
|---|---|---|---|
| Storwize V7000 Gen2 or Storwize V7000 Gen2+ 2U control enclosure | 24 2.5-inch solid-state drives, 2 host adapters, and 2 compression accelerators | 452 W | 1542 |
| 24 10 K SAS drives, 2 host adapters, and 2 compression accelerators | 430 W | 1467 | |
| 24 15 K SAS drives, 2 host adapters, and 2 compression accelerators | 471 W | 1607 | |
| 2U expansion enclosure | 24 2.5-inch flash drives | 151 W | - |
| 24 10 K SAS drives | 175 W | - | |
| 24 15 K SAS drives | 234 W | - | |
| 2U expansion enclosure | 12 7.2 K nearline SAS drives | - | |
| 5U expansion enclosure | 92 10 TB nearline SAS drives | 848 W | - |
| 5U expansion enclosure | 92 15 TB tier 1 flash drives | 748 W | - |
Each control enclosure contains two PSUs for redundancy. The total power consumption values represent the total power that is drawn by both PSUs.
Environmental requirements
| Environment | Ambient temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating | 5°C to 40°C (41°F to 104°F) | 0 - 2133 m (0 - 7000 ft) |
8% to 80% noncondensing | 23°C (73°F) |
| 5°C to 35°C (41°F to 95°F) | 2134 - 3048 m (7001 - 10000 ft) |
|||
| Non-operating | 1°C to 50°C (34°F to 122°F) | -305 to 12192 m
(-1000 to 40000 ft) |
8% to 80% noncondensing | 27°C (80°F) |
| Storage | 1°C to 60°C (34°F to 140°F) | 5% to 80% noncondensing | 29°C (84°F) | |
| Shipping | -40°C to 60°C (-40°F to 140°F) | 5% to 100% condensing, but not precipitating |
Dimensions and weight
| Enclosure | Height | Width | Depth | Maximum weight | |
|---|---|---|---|---|---|
| Drive ready (without drive modules) | Fully configured (with drive modules) | ||||
| 2U control enclosure with 24 drive slots | 87 mm (3.46 in.) | 483 mm (19.0 in.) | 730 mm (28.7 in.) | 28.2 kg (62.1 lb) | 36.5 kg (80.5 lb) |
| 2U expansion enclosure with 12 drive slots | 556 mm (21.9 in.) | 16.4 kg (36.2 lb) | 26.7 kg (58.9 lb) | ||
| 2U expansion enclosure with 24 drive slots | 556 mm (21.9 in.) | 16.7 kg (36.8 lb) | 25.0 kg (55.1 lb) | ||
| 5U expansion enclosure with 92 drive slots | 222.2 mm (8.75 in.) | 483 mm (19.0 in.) | 968 mm (38.1 in.) | 67 kg (147.7 lb) | 135 kg (297 lb) |
- When you are powering off a 92F, 92G, or an A9F 5U expansion enclosure because you intend to transport it to another location
- When you intend to move a rack that contains a 92F, 92G, or an A9F 5U expansion enclosure

Additional space requirements
Ensure that these additional space requirements, as shown in Table 5, are available around the enclosures.
| Location | Additional space requirements | Reason |
|---|---|---|
| Left and right sides | 50 mm (2 in.) | Cooling air flow |
| Back | Minimum: 100 mm (4 in.) (This is not needed for 5U expansion enclosure.) | Cable exit |
Supported drives
The Storwize V7000 Gen2 and Storwize V7000 Gen2+ models support up to 504 drives in the system with RAID levels 0, 1, 5, 6, and 10. For more imformation about the supported drives, see Replaceable units.
Acoustical specifications for SAS drives for each control enclosure
| Model and type | Acoustical output per enclosure |
|---|---|
| 2U expansion enclosure with 24 2.5-inch drive slots | Less than 6.5 B LwA -- Operating (40% Average seek rate) @ 23°C ambient |
| 2076-524 /2076-624 /2076-U7A control enclosure with 24 2.5-inch drive slots | Less than 6.3 B LwA – Operating (40% Average seek rate) @ 23°C ambient |
| Model and type | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idling | Operating | Idling | |
| Fully-configured 5U expansion enclosure (92 drives) | 8.5 | 8.5 | 85 | 85 |
|
Notes:
Important: Government regulations (such as those prescribed by OSHA or European
Community Directives) may govern noise level exposure in the workplace and may apply to you and your
server installation. This system is available with an optional acoustical door feature that can help
reduce the noise emitted from this system. The actual sound pressure levels in your installation
depend upon a variety of factors, including the number of racks in the installation; the size,
materials, and configuration of the room where you designate the racks to be installed; the noise
levels from other equipment; the room ambient temperature, and employees' location in relation to
the equipment. Further, compliance with such government regulations also depends upon a variety of
additional factors, including the duration of employees' exposure and whether employees wear hearing
protection. IBM® recommends that you consult with qualified
experts in this field to determine whether you are in compliance with the applicable
regulations.
|
||||
The noise emission level that is stated is the declared (upper limit) sound power level, in decibels, for a random sample of machines. All measurements are made in accordance with ISO 7779 and reported in conformance with ISO 9296.
Shock and vibration specifications for control enclosures
Table 8 and Table 9 provide the shock and vibration testing results for your control enclosure.
| Shock categories | Test level | Performance |
|---|---|---|
| Operational | 5 g 10 ms 1/2 Sine | <= 25 g 10 ms |
| Non-operational | 30 g 10 ms 1/2 Sine | <= 75 g 11 ms |
| Vibration categories | Test level | Performance |
|---|---|---|
| Operational | 0.21 grms 5-500 Hz Random | Throughput loss < = 10% FCAL < = 0.68 grms |
| Non-operational | 1.04 grms 2-200 Hz Random | <= 3.12 grms |
| Shipping | 0.3 g 2-200 Hz Sine | <= 5 g |
| Rotational vibration | Normal operation performance measurements in enclosure with no external vibration. | Throughput loss for all drives of the same type within performance profile. |