You can remove either of the redundant power supply units in a 5U expansion enclosure.
Redundant power supplies operate in parallel; one continues to provide power to the enclosure if the
other fails.
Before you begin
Important: You can remove a PSU without powering off the expansion enclosure. However,
to maintain operating temperature, ensure that you perform the following tasks.
Do not remove a faulty PSU until its replacement is ready to be installed.
Do not remove a PSU from an operational enclosure for more than approximately 10 minutes. The
reduction in airflow through the enclosure might cause the enclosure or its components to shut down
to protect from overheating.
About this task
Each PSU provides cooling to the lower part of the enclosure. Ensure that the second PSU
in the enclosure is powered on and operating correctly. For example, in Figure 1, PSU 1 is operating while PSU 2 is being removed.
Review and follow the procedures for handling static-sensitive devices before you remove the
power supply unit (PSU).
Procedure
Read all safety information.
Remove the 1U fascia that covers the PSUs on the front of the expansion enclosure, as described
in Removing the fascia.
Press on the handle lock to release the handles on the PSU.
Carefully pull the PSU out of the expansion enclosure chassis and place it in a safe location,
as shown in Figure 2.
Figure 2. Removed power supply
If you are instructed to return the power supply, follow all packaging instructions. Use any
packaging materials for shipping that are supplied to you.